Single-stage versus variable-speed air conditioning dehumidification performance

After an exciting summer packed with three blower motor failures in three 6-year-old Trane single-speed air conditioning systems, the transformation of our house into a showcase for variable-speed communicating Trane/American Standard equipment is complete.

For background, see the folllowing:

The most humid part of our house was the upstairs. This contains two big bedrooms served by a 3-ton A/C for a calculated Manual J demand of 2.1 tons. Relative humidity was 58-62 percent with a TEM6 variable-speed air handler and a single-stage condenser.

Step 1 was replacing the condenser with a variable-speed “communicating” condenser that sends digital information back to the air handler over a two-conductor cable. Trane says that this new condenser is a match for the 6-year-old TEM6 so long as an adapter relay panel is installed. What they don’t say is that the result is a brain-dead system in which the air handler always runs at the same blower speed regardless of what the compressor speed is. Compared to the 6-year-old single-stage A/C, there was no reduction in humidity from this arrangement.

Step 2 was replacing the (working perfect with a new blower) TEM6 air handler with a top-of-the-line TAM9 air handler. Humidity immediately plummeted to a reasonable 51 percent on a wet hot Florida day with hours of rain, an 87-degree high, and humidity as high as 95 percent.

What does #Science say about this result? “Dehumidification performance of a variable speed heat pump and a single speed heat pump with and without dehumidification capabilities in a warm and humid climate” (Kone and Fumo 2020; Energy Reports):

the variable speed mode was able to maintain relative humidity between 50% to 52% on summer days. In the single-speed with enhanced dehumidification, a slightly less effective humidity control was achieved on summer days with the mode keeping the relative humidity between 53% to 55%. In the normal cooling mode, which resembles a conventional system, the humidity levels were controlled between 55% to 60%. In the shoulder season, the variable speed and enhanced dehumidification modes maintained the relative humidity between 55% to 58% and 53% to 56% respectively. In the shoulder season, the normal cooling mode kept the indoor relative humidity near or above 60%.

In going from single-stage to variable-speed, #Science found a reduction in humidity from an average of 57.5% to 51% (middle of the ranges given), or 6.5%. My data, consistent from a Govee sensor set and a $300 Airthings monitor, was 8-10% reduction in the relative humidity reading. The ground floor of the house still feels and measures less humid (40-50% depending on the location), but walking upstairs no longer feels like entering a steam room.

It’s tough to find objective data from anywhere else. Carrier is the only company, I think, that offers any numbers:

The Trane stuff has an emergency dehumidification capability in which it will run the heat strips as the same time as the A/C. Carrier also might have something like this (their commercial systems have a “reheat” mode that might do something similar, but using only the coil and not the resistive heat strips).

It is unclear from the Carrier page if they’re talking about using an extreme measure to dehumidify or just running the variable-speed in an optimized manner.

I’m also unclear what they mean by “400 percent more moisture” removed. If a single-stage system is removing 1 gallon of water, the variable-speed system removes 5 gallons when outside temp and thermostat temp are held constant? That doesn’t seem plausible. If it is hot and humid outside, the system has to remove a huge amount of water just to do its basic job (since cooling outside air will almost immediately result in 100% relative humidity and condensation).

If relative humidity is linear in the amount of water vapor, a properly sized single-stage system has already removed more than half the water that was originally present in the air (since cooling resulted in 100% relative humidity and the house ended up at 50% humidity). As great as Carrier may be (they’re headquartered only about two miles from our house here in Palm Beach County!), I don’t see how they can remove 5X the amount of water compared to a system that removes half of the water available.

(Why didn’t we get Carrier? We already had Trane gear and thought that we might be able to preserve at least some of it (we weren’t). Also, the Carrier dealer who came out to quote the project refused to deal with our house because of a splice where the wires exit the house near the condenser, claiming that their communication wouldn’t function properly.)

I can’t figure out why single-stage A/C continues to be the standard here in the U.S. Everyone in Asia has variable-speed equipment (all of the mini splits are variable-speed). Assuming a constant thermostat setting, a single-stage system is the correct size for only one outdoor temperature. Why wouldn’t people be willing to pay a little more for a system that can run at the correct speed for whatever temp Climate Change happens to dish out at any given hour on any given day? Is it that it is impossible to explain to consumers what a dumb idea single-stage A/C is? (Maybe it makes sense in Arizona, though, where there isn’t any humidity to begin with?)

11 thoughts on “Single-stage versus variable-speed air conditioning dehumidification performance

    • Ted: what does a Carrier system actually do that is different than what Trane and Lennox do? Note that you can’t retrofit a heat pump into a Florida house because the return line is not insulated so cold refrigerant in it will cause condensation.

  1. FDM printing requires humidity below 30% for a long print. It would be an expensive proposition even with a Greenspun level A/C system. Most of the FDM fans live in the midwest manufacturing belt so there’s no real knowledge of how to dehumidify the complete filament path.

  2. HVAC manufacturers have too strong of a cartel in the US, there is not much choice of product available to the consumer.
    Also, (like medicine) most people are not really knowledgeable enough to specify HVAC on their own so they live on the kindness of strangers (in the cartel)

  3. But why dehumidify? Just cool upstairs to the lower temperature so it feels fine even with high humidity.

    In Seattle I have different problem, btw. We actually humidity in the winter.

    • SK: I think I tried cooling the upstairs to a frigid 68 and it was still pretty humid. As the January 6 insurrectionists are to a noble democracy-loving Democrat, mold is to the Florida homeowner: an ever-present and pernicious enemy that will exploit any crack in an attempted defense. The mold zone starts at 60 percent relative humidity. “If there are no cold-condensing surfaces and the relative humidity (RH) is maintained below 60 percent indoors, there will not be enough water in those materials for mold to grow. However, if the RH stays above 70 percent indoors for extended periods of time, mold will almost certainly grow.” — https://epi.dph.ncdhhs.gov/oee/mold/conditions.html

  4. At the risk of adding noise and ruining your décor and feng shui, a dedicated 50-pint dehumidifier with a built-in pump (the pump is crucial).

    The one I bought at Menard’s years ago is doing great. The capacity ratings have become more stringent, so the reported performance numbers will be lower than in the past even if the actual performance has not changed.

    • FB: You’d think that a dehumidifier would be standard issue for Florida houses. I would certainly put one in just for flexibility if I were designing a house from scratch.

      There is no accessible attic above our upstairs bedrooms (the air handler for this part of the house is shoehorned into a closet), so it would require some creativity and sheetrock work to place a dehumidifier. Code requires that the dehumidifier have its own drain and not share with an air handler, so it wouldn’t be a code-compliant installation (retrofitting a drain line is not practical in my opinion unless it was part of a gut-rehab of the house). I stuck a 50 pint/day portable dehumidifier (borrowed from a kind neighbor) in a shower stall up there and it didn’t generate a huge improvement. I think it would have to be at least 100 pints/day to “make a difference” (as the progressives like to say).

      If you put use 90 degrees outside with 80 percent relative humidity and 72 inside with 60 percent, with 800 CFM (standard for a 2-ton single-stage, I think) into

      https://www.adicotengineering.com/condensate-calculator

      you get that it is producing 1,136 pints/day of condensate(!). I’m not sure that I believe this. That’s 6 gallons per hour and a bucket placed under a condensate drain doesn’t fill up that fast. Maybe the answer is that this is what would be produced if you exhausted all of the air from your house at 800 CFM at the same time you were cooling outside air (i.e., there was no recirculation).

      https://waypointinspection.com/how-much-water-drain-from-air-conditioner/

      says 5-20 gallons per day. Let’s assume 20 in Florida! That’s 160 pints per day. The typical family-sized house has two A/C systems, so that’s 320 pints per day. Therefore, a 50-pint machine won’t have a dramatic effect.

  5. We put a whole house dehumidifier in along with our Carrier Infinity system on the main floor of our house. It connects to the same ductwork as the main system and is far more efficient than a small plug in dehumidifier. Our humidity in the house is now quite low, to the point where we can leave the temp higher and still be quite comfortable.

    Here’s the unit we installed:

    https://www.aprilaire.com/whole-house-products/dehumidifiers/e100-dehumidifier

    • Anon: What did you do for the dehumidifier drain? Did you run a new line or dump the water into an existing condensate drain that is shared with an air handler?

    • A new drain line was run. It runs parallel to the existing drain line from the air handler. It was easy to do as both units are in the basement so access was simple.

Comments are closed.